Ducts First, Furnace Second
When a Brooklyn Center homeowner calls about a bedroom that never warms up, the furnace is rarely the problem. Most of these ramblers and split-levels were built with a single central return and short, small branch ducts, sized for a furnace that only heated. Add a coil for central air, then a higher-efficiency furnace with a tighter heat exchanger, and the same ducts now carry more resistance than they were drawn for.
Start with a static pressure reading and a look at the return. If total static is well above what the blower is rated for, a bigger furnace makes things worse, and the fix is usually an added return, a larger filter cabinet, or a damper adjustment on the long runs. The furnace gets sized after that, with a load calculation.